Connecting The Grounding Electrode Conductor To Rebar

November 30, 2005

Q: Where reinforcing steel in a concrete slab that is in contact with the earth is used as a grounding electrode, may the grounding electrode conductor be clamped to a rebar within the concrete or must the connection be made on the outside of the concrete?

A: Generally, the connection of the grounding electrode conductor to the grounding electrode must be accessible. However, 250.68(A) has an exception to this requirement. “Exception – An encased or buried connection to a concrete encased, driven or buried grounding electrode shall not be required to be accessible.”

When the connection will be encased in concrete, an inspection should be made before concrete is poured, and the ground clamp must be marked to indicate that it is suitable for direct burial. A clamp that is suitable for concrete encasement is amrked “direct burial” or “DB.” I would recommend exothermic welding.

Normal practice is to have the general contractor turn up 6 to 12 inches of reinforcing steel rod on both sides of the proposed building if the location of the service is unknown to permit the electrical contractor to connect the grounding electrode conductor to the rebar when electricians arrive at the construction site.

Get the Tools and Guidance You Need to SAFELY and Successfully Complete ALL of Your “Do-It-Yourself” Home Wiring & Installation Projects from a Master Electrician with Over 20 Years Experience by visiting www.gilchrist-electric.com today.

DIY Electrical Wiring Help from a Master Electrician Do you need assistance with your electrical wiring project? Please visit my DIY Electrical Wiring Help from a Master Electrician page. Where I provide electrical wiring tips, expert electrical advice, answers to your electrical questions and electrical consulting & design services over the phone, via instant messenger or via email.

If you enjoyed this post, make sure you subscribe to my RSS feed or receive updates via email. You can also follow me on Twitter and "LIKE" me on Facebook.

Similar Posts:
Site Sponsor
The Electrical Tool Store - Your online source for electrical wi


Comments

Do you have a question or idea to add to this post? Feel free to post it below. Due to a large backlog and an overwhelming response, it takes approximately 30 days to receive an answer to your electrical question for free. Simply subscribe to this blog (use one of the subscription methods listed in the top right corner of this page) and your answer will be listed in a new blog post in the near future.

To receive an immediate answer (in less than 24 hours) please visit my DIY Electrical Wiring Help from a Master Electrician page.






× four = 36

Bottom