Q: Does Article 230 apply to the conductors and overcurrent protection from a standby generator located outdoors about 20 feet from the building it serves?

A:No, Article 230 applies to services, and the definition of a service, which appears in Article 100, reads: “Service. The conductors and equipment for delivering electric energy from the serving utility to the wiring system of the premises served.” The key words in this definition are “serving utility;” therefore, Article 230 does not apply.

Article 445 covers generators and references Article 695, 700, 701, 702 and 705, which must be complied with depending on the generator’s use. Alternating current machines must be protected from overloads by inherent design, fuses, circuit breakers or other acceptable overcurrent protection.

Supply-conductor ampacity from the generator to the overcurrent protection cannot be less than 115 percent of the nameplate current rating of the generator. These requirements appear in 445.12(A) and 445.13.

If the standby generator supplies a fire pump, additional requirements for the generator set are found in Article 695. A generator used to supply emergency power must comply with the rules in Article 700, especially 700.12(B).

Requirements for a legally required standby system are similar in some respects to those in Article 700 and are in Article 701. If the generator is connected to optional standby loads, Article 702 applies. Where the generator operates in parallel with the utility system, Article 705,Interconnected Electric Power Production Sources applies. Each Article has different requirements but they all prohibit inadvertent parallel operation of the generator with the utility system.

Visit our web site today to see our large selection of Generac Guardian Home Standby Generators. Financing is available for all of our generators.

Do you have an electrical question you would like us to answer? We will answer the first question posted to this blog daily. Your answer will be posted in the next day’s blog. If you need your question answered sooner, visit www.gilchrist-electric.com

DIY Electrical Wiring Help from a Master Electrician Do you need assistance with your electrical wiring project? Please visit my DIY Electrical Wiring Help from a Master Electrician page. Where I provide electrical wiring tips, expert electrical advice, answers to your electrical questions and electrical consulting & design services over the phone, via instant messenger or via email.

If you enjoyed this post, make sure you subscribe to my RSS feed or receive updates via email. You can also follow me on Twitter and "LIKE" me on Facebook.

Similar Posts:
Site Sponsor
The Electrical Tool Store - Your online source for electrical wi


Comments

Do you have a question or idea to add to this post? Feel free to post it below. Due to a large backlog and an overwhelming response, it takes approximately 30 days to receive an answer to your electrical question for free. Simply subscribe to this blog (use one of the subscription methods listed in the top right corner of this page) and your answer will be listed in a new blog post in the near future.

To receive an immediate answer (in less than 24 hours) please visit my DIY Electrical Wiring Help from a Master Electrician page.






four − 2 =

Bottom