Can I Use # 4 NMB To Feed A 100 Amp Subpanel?

March 20, 2006

Q: What is the ampacity of # 4 AWG copper NMB cable when used as the main feeder to supply a branch circuit panelboard in a single family home? The service conductors are three # 4 AWG copper conductors with Type THWN insulation in 1 inch rigid metal conduit protected by a 100A main circuit breaker.

A: Type NMB cable has conductors that have an insulation rating of 90 C. However, 334.80 limits the ampacity to the values shown in Table 310-16 for 60 C insulation, but if the conductors must be derated, the 90 C ampacity is permitted to be used provided the final derated ampacity does not exceed the ampacity for 60 C conductors. To further confuse the issue, this sentence appears in 320/15(B)(6): “The feeder conductors to a dwelling unit shall not be required to be larger than their service-entrance conductors.” Based on these various NEC references, the electrical inspector should accept the 4 AWG copper NMB cable as a 100A feeder. Because this is an area that is not very clear, you should check with the authority having jurisdiction before making this installation.

DIY Electrical Wiring Help from a Master Electrician Do you need assistance with your electrical wiring project? Please visit my DIY Electrical Wiring Help from a Master Electrician page. Where I provide electrical wiring tips, expert electrical advice, answers to your electrical questions and electrical consulting & design services over the phone, via instant messenger or via email.

If you enjoyed this post, make sure you subscribe to my RSS feed or receive updates via email. You can also follow me on Twitter and "LIKE" me on Facebook.

Similar Posts:
Site Sponsor
The Electrical Tool Store - Your online source for electrical wi


Comments

Do you have a question or idea to add to this post? Feel free to post it below. Due to a large backlog and an overwhelming response, it takes approximately 30 days to receive an answer to your electrical question for free. Simply subscribe to this blog (use one of the subscription methods listed in the top right corner of this page) and your answer will be listed in a new blog post in the near future.

To receive an immediate answer (in less than 24 hours) please visit my DIY Electrical Wiring Help from a Master Electrician page.






nine − 1 =

Bottom