Terminating Aluminum Wire

April 1, 2006

Q: Is there a requirement in the National Electrical Code (NEC) for the use of an oxide inhibitor on aluminum conductor terminations? Some lugs are provided with an antioxidant paste supplied by the manufacturer and some are not. Some cable and wire terminal manufacturers that do not provide a compound in the lug suggest that an antioxidant paste be used but do not require it.

A: There is no rule in the NEC that requires an oxide inhibitor at all aluminum wire terminations. In fact, this sentence appears in Section 110.14 of the Code: “Materials such as solder, fluxes, inhibitors and compounds where employed, shall be suitable for the use and shall be of a type that will not adversely affect the conductors, insulation or equipment.”

This information appears in the General Information for Electrical Equipment Directory (White Book) published by Underwriters Laboratories Inc. under the title Wire Connectors and Soldering Lugs (ZMVV): “Some connectors are shipped prefilled with conductor termination compound (antioxidant compound). For non-prefilled connectors, conductor termination compound may be used if recommended by the connector manufacturer as preliminary preparation of the conductor. Wire brushing of the conductor may also be performed if recommended.”

Underwriters Laboratories listed conductor termination compounds are available. These compounds retard oxidation at the connector-conductor interface, and they do not have an adverse effect on the conductor metal, insulation or equipment.

DIY Electrical Wiring Help from a Master Electrician Do you need assistance with your electrical wiring project? Please visit my DIY Electrical Wiring Help from a Master Electrician page. Where I provide electrical wiring tips, expert electrical advice, answers to your electrical questions and electrical consulting & design services over the phone, via instant messenger or via email.

If you enjoyed this post, make sure you subscribe to my RSS feed or receive updates via email. You can also follow me on Twitter and "LIKE" me on Facebook.

Similar Posts:
Site Sponsor
The Electrical Tool Store - Your online source for electrical wi


Comments

One Response to “Terminating Aluminum Wire”

  1. Anonymous on April 15th, 2006 2:44 pm

    We recently had a physical inspection on our southern Californai home as we are in escrow. Our 1968 home has alumimum wiring throughout. As part of a major remodel, a licensed electrical contractor pigtailed all the interior switches and plugs.

    We had them add a new electrical panel at the time of the remodel. Recently the physical inspector reported that their is aluminum branch wiring at the panel. He said that normally, he sees antioxidant paste where the aluminum wiring connects to the breaker lugs, but in our panel, found none.

    Should this be something that the electrical contractor should have done?

    Regards,
    Kacey Brumley
    krbrumley@adelphia.net

Do you have a question or idea to add to this post? Feel free to post it below. Due to a large backlog and an overwhelming response, it takes approximately 30 days to receive an answer to your electrical question for free. Simply subscribe to this blog (use one of the subscription methods listed in the top right corner of this page) and your answer will be listed in a new blog post in the near future.

To receive an immediate answer (in less than 24 hours) please visit my DIY Electrical Wiring Help from a Master Electrician page.






7 − = one

Bottom