Q: May I install romex in a 2 inch metal conduit that is 24 inches long into a panel without securing the cables within 12 inches of where they enter the panel?

A: The general requirement for cable termination is in 312.5(C). This one sentence rule says: “Where cable is used, each cable shall be secured to the cabinet, cutout box, or meter socket enclosure.” However, there is a long exception for nonmetallic sheathed cable (romex), and it is pretty detailed.

Nonmetallic sheathed cables are permitted to enter the top of a service mounted panelboard through a nonflexible raceway that is not less than 18 inches long or longer than 10 feet.

The cable must be secured within 12 inches of the outer end of the raceway; the raceway must extend directly above the panelboard and cannot penetrate the structural ceiling; a fitting is required at each end of the raceway to protect the cables from abrasion and the fittings must remain accessible after installation; the raceway must be sealed at its outer end; the cable sheath must be continuous in the raceway and extend into the panelboard beyond the fitting for at least 1/4-inch; the raceway is secured in accordance with the requirements of the applicable article for the wiring method; and the wire fill table in Chapter 9 must be used to prevent cable overfill.

To determine the number of cables permitted in the 2 inch conduit, Note 9 to Table 1 in Chapter 9 requires that multiconductor cables be treated as a single conductor. For cables with oval or elliptical cross sections, the cross-sectional area is based on the major diameter of the ellipse to obtain an equivalent circle diameter.

Do you have an electrical question you would like us to answer? We will answer the first question posted to this blog daily. Your answer will be posted in the next day’s blog. If you need your question answered sooner, visit www.gilchrist-electric.com

DIY Electrical Wiring Help from a Master Electrician Do you need assistance with your electrical wiring project? Please visit my DIY Electrical Wiring Help from a Master Electrician page. Where I provide electrical wiring tips, expert electrical advice, answers to your electrical questions and electrical consulting & design services over the phone, via instant messenger or via email.

If you enjoyed this post, make sure you subscribe to my RSS feed or receive updates via email. You can also follow me on Twitter and "LIKE" me on Facebook.

Similar Posts:
Site Sponsor


Comments

Comments are closed.

Bottom